Introduction
ST-9001D16 Three Phase Electric Energy Meter Testing Equipment is designed according to state standards, rules and requirement for whole automation testing equipment. It adopts Henan STAR Hi-tech Co. advanced designed large power three phases testing power source and reference meter. It could provide for manufacture, power supply departments, and metrology departments to test and calibrate electronic type or mechanic type three phase three wire, three-phase four-wire active energy meter sand reactive energy meters.
Main Function
Its operated by PC (or the equipment with keyboard)
The equipment adopts test by comparison method could operate by manual or animation complete test for under testing meter and auto print out testing results. It could test16 sets different meter constant meters simultaneously
The customer according to the requirement of rules any select current loading points fordifferent under testing meter to auto test
When manual test with reline testing points, phase with eight testing point frequency testing points same as the power supply, such testing points simplify testing work greatly
The equipment could test under testing meter by four quarter, the reactive standard is sine reactive standard
The equipment with high and low pulse output ports of reference meter and could reverse testDigital display output voltage, current, power, phase and frequency
Output voltage and current could any 2~21th harmonics. The harmonics could set in split phase or by voltage and current. Any phase output with multi-harmonics
With current ranges auto transfer function. The customer according to under testing meter rated current to select range within 0~120A
Output voltage and current soft on/off. Output voltage short circuit or output current open circuit auto protection and indicate the fault point
Output voltage by star connection, output current by floating point. (Three phase three wire voltage output by U connection)
Current inner CT active compensation with small size and high accuracySingle power source supplyIt adopts module structure with independent operation easy to calibration, maintenance and upgrade
Specifications
Equipment accuracy is 0.1 classes. The total error no more then the
equipment class80%
Voltage divided into 4 ranges: 57.7V, 100V, 220V, 380V. Each range continues adjusting to 120% rated value
Current divided into 12 ranges: 0.1A, 0.25A, 0.5A, 1A, 1.5A, 3A, 5A, 10A, 15A, 30A, 60A,120A.
Each range continues adjusting to 120%rated value
Output current with IMAX, 400%, 200%, 150%, 100%, 50%, 20%, 10%, and 5%, nine testing points
Frequency ranges: 45~65Hz, step adjusted by 0.0Hz. It could setting directly also
Phase ranges: 0~359.9, step adjusted by 0.01. It could set directly also
Phase testing points: cos/sin =0.5C,0.8C, 1C, 1L, 0.8L, 0.5L, shown as vector diagram(1).
Three phase symmetry less than+_0.5
Output voltage, current and power stability less than 0.02% (cos=1,3min)
Output voltage (current) wave form distortion,<0.5%(for voltage 300W,current 600w)
Output voltage (current) ratio display by 3 digit, accuracy +_5%
Max consumption: 5000VA
Harmonic amplitude from 0~100% basic wave is setted by 1% Harmonic phase from 0~359, resolution 1
Power supply: 220V+_10% AC50Hz
Environment temperature: 20+_2, F.H<85%
See more products from this supplier.
Do you want to show products of your own company? Join FREE now!